Inner Corner at Base of Wall Wappingers Falls NY

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry.

Local Companies

Allied Builders Supply Corp
(516) 826-9057
3550 Merrick Rd
Seaford, NY
Lari Construction Limited
(315) 701-0444
2572 Erie Blvd E
Syracuse, NY
Russo Joe Mason Contractor
(914) 939-7395
424 Glen Ave
Port Chester, NY
Ponselle Brothers Inc
(631) 331-2540
186 Miller Place Rd
Miller Place, NY
Hampton Brick Works
(631) 723-2821

Hampton Bays, NY
Blue Ribbon Contracting & Design Inc
(631) 744-7555
66 Route 25A
Shoreham, NY
Casler Masonry Inc-Warehouse
(315) 253-5374
692 Cayuga Rd
Cayuga, NY
Bierwagen David Rpt
(315) 422-7656
550 Harrison St
Syracuse, NY
Bibeau Marcel Mason Contr
(518) 561-0076
37 Latour Ave
Plattsburgh, NY
De Ridder Masonry Inc
(518) 584-2666
59 Blanchard Rd
Gansevoort, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: September 1, 2006

By Walter A. Laska

It is difficult for a mason to properly tool mortar joints at inner wall corners due to the size and shape of the jointer and the acute angle formed by the intersecting brick. As a result, the mortar joints at this location cannot be tooled neatly or compactly. Therefore, inner wall corners provide an ideal location for expansion joints.

Expansion joints located at inner corners are easy to construct and are well concealed. The expansion joint should be totally void of any material which might inhibit movement, and the reinforcement must be discontinuous at the expansion joint.

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry. Also, the connection creates a control joint in the concrete masonry backing along the column interface.
Elevation View

The space between the column and the concrete masonry should be kept free of all mortar bridging. If the column and concrete masonry are tightly bonded, any movement of the column is transferred to the masonry, possibly causing the concrete masonry backing to crack.

Flashing continuity must be maintained at the inner corners. The flashing should be cut, lapped, and set in a continuous bed of mastic to prevent water from flowing under the laps.