Inner Corner at Base of Wall Oceanside NY

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry.

Local Companies

SLR Industries Inc.
631 893 3934
411 Broadway
West Babylon, NY
Malatesta Paladino Inc
(718) 523-5656
13919 109th Ave
Jamaica, NY
Fort Hill Landscape And Design Inc
(631) 271-8651
151 New York Ave
Huntington, NY
Obama Inc
(718) 321-0380
13225 Maple Ave
Flushing, NY
SLR Industries Inc.
631 893 3934
411 Broadway
West Babylon, NY
Hatiya Contracting Inc
718-395-7744
9322 74th Place
Woodhaven, NY
A La Marca Construction
(718) 526-7795
14402 91st Ave
Jamaica, NY
Capstone Construction
(631) 784-7701
775 Park Ave
Huntington, NY
Prima Plastering Inc
(631) 427-8699
77 Soundview Rd
Huntington, NY
Pezzino Nely
(718) 358-1481
2221 Parsons Blvd
Flushing, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: September 1, 2006

By Walter A. Laska

It is difficult for a mason to properly tool mortar joints at inner wall corners due to the size and shape of the jointer and the acute angle formed by the intersecting brick. As a result, the mortar joints at this location cannot be tooled neatly or compactly. Therefore, inner wall corners provide an ideal location for expansion joints.

Expansion joints located at inner corners are easy to construct and are well concealed. The expansion joint should be totally void of any material which might inhibit movement, and the reinforcement must be discontinuous at the expansion joint.

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry. Also, the connection creates a control joint in the concrete masonry backing along the column interface.
Elevation View

The space between the column and the concrete masonry should be kept free of all mortar bridging. If the column and concrete masonry are tightly bonded, any movement of the column is transferred to the masonry, possibly causing the concrete masonry backing to crack.

Flashing continuity must be maintained at the inner corners. The flashing should be cut, lapped, and set in a continuous bed of mastic to prevent water from flowing under the laps.

Click here to read full article from Masonry Construction