Inner Corner at Base of Wall Jamestown NY

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry.

Local Companies

Green Isle Contrctng
(516) 488-3800
153A Woodbine Ct
Floral Park, NY
Sam's Masonry Corp
(631) 451-0622
14 Hickory Ave
Farmingville, NY
Barber W & M
(631) 928-7401
19 S Columbia St
Port Jefferson Station, NY
Rjc Contracting Corp
(631) 265-5448
19 Hillcrest Dr
Smithtown, NY
Carmody Building Corp
(845) 352-2299
145 College Rd
Suffern, NY
Spinks Craig
(607) 583-2570
8833 W Waneta Lake Rd
Hammondsport, NY
Jdr Masonry Services
(518) 785-7947
11 Bittersweet Ln
Clifton Park, NY
Vicent & Sons Masonary
(631) 267-6032
112 Watersedge
East Hampton, NY
Creative Brick
(914) 375-2965
150 Harrison Ave
Yonkers, NY
N & D Masonry Corp
(631) 585-1515
281 Cenacle Rd
Ronkonkoma, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: September 1, 2006

By Walter A. Laska

It is difficult for a mason to properly tool mortar joints at inner wall corners due to the size and shape of the jointer and the acute angle formed by the intersecting brick. As a result, the mortar joints at this location cannot be tooled neatly or compactly. Therefore, inner wall corners provide an ideal location for expansion joints.

Expansion joints located at inner corners are easy to construct and are well concealed. The expansion joint should be totally void of any material which might inhibit movement, and the reinforcement must be discontinuous at the expansion joint.

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry. Also, the connection creates a control joint in the concrete masonry backing along the column interface.
Elevation View

The space between the column and the concrete masonry should be kept free of all mortar bridging. If the column and concrete masonry are tightly bonded, any movement of the column is transferred to the masonry, possibly causing the concrete masonry backing to crack.

Flashing continuity must be maintained at the inner corners. The flashing should be cut, lapped, and set in a continuous bed of mastic to prevent water from flowing under the laps.