Inner Corner at Base of Wall Corning NY

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry.

Local Companies

Austin Don Masonry
(315) 592-5278
54 Wood Ridge Ln
Fulton, NY
Will & Will General Contractors
(716) 433-4304
6035 S Transit Rd
Lockport, NY
Long Island Pool Scapes
(631) 698-8873
2 Avalon Ct
Ronkonkoma, NY
Fratelli Constr Corp
(631) 207-9164
76 Middle Island Ave
Medford, NY
Darcom Inc
(516) 872-3798
49 Dubois Ave
Valley Stream, NY
Arcade Contracting & Restoration Inc
(718) 596-4030
615 Degraw St
Brooklyn, NY
Nethercott P W Inc
(914) 939-2383
433 W William St
Port Chester, NY
Heady Kenneth Contractor
(845) 226-8589
Cottontail Ln
Hopewell Junction, NY
Atomic Brick-Interlocking Paving
(631) 261-0554
16 Hasty Ln
Greenlawn, NY
Colonial Masonry Corp
(212) 477-5910
215 Park Ave S Ste 2010
New York, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: September 1, 2006

By Walter A. Laska

It is difficult for a mason to properly tool mortar joints at inner wall corners due to the size and shape of the jointer and the acute angle formed by the intersecting brick. As a result, the mortar joints at this location cannot be tooled neatly or compactly. Therefore, inner wall corners provide an ideal location for expansion joints.

Expansion joints located at inner corners are easy to construct and are well concealed. The expansion joint should be totally void of any material which might inhibit movement, and the reinforcement must be discontinuous at the expansion joint.

The concrete masonry can be connected to the corner column with a debonded shear anchor. This type of anchor resists out-of-plane (but not in-plane) shear forces and permits movement between the steel column and concrete masonry. Also, the connection creates a control joint in the concrete masonry backing along the column interface.
Elevation View

The space between the column and the concrete masonry should be kept free of all mortar bridging. If the column and concrete masonry are tightly bonded, any movement of the column is transferred to the masonry, possibly causing the concrete masonry backing to crack.

Flashing continuity must be maintained at the inner corners. The flashing should be cut, lapped, and set in a continuous bed of mastic to prevent water from flowing under the laps.