Flashing Factors Potsdam NY

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments in Potsdam.

Local Companies

Darius Masonry Inc
(631) 841-3234
500 Marconi Blvd
Copiague, NY
Fladd's Creative Store
(585) 554-3066
322 Gray Rd
Rushville, NY
Ridge Paving Inc
(914) 234-6567
31 Bedford Banksville R
Bedford, NY
Moe Masonry Inc
(631) 287-4887
100 Sandy Hollow Rd
Southampton, NY
Gould Laura
(845) 651-5421
346 Reservoir Rd
Goshen, NY
Green Lawn Garden Center
(914) 682-4848
454 Ridgeway
White Plains, NY
Pcc Contracting Inc
(518) 785-8000

Albany, NY
Luis Mason Contractor Ltd
(914) 476-0550
406 Saw Mill River Rd
Yonkers, NY
Manley Construction Corp
(718) 389-5365
300 Eckford St
Brooklyn, NY
Ml Stumpf Contractng
(631) 580-0078
21 Wade Dr
Lake Grove, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: October 1, 2005

Should flashing be used beneath rowlock brick window sills? If through-wall flashing is installed beneath these rowlocks, how are the sills anchored? If the anchors penetrate the flashing, does this lead to deterioration of the masonry below in freeze-thaw environments?

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments.

When they are used in freeze-thaw environments, however, the flashing beneath them is critical to prevent water from saturating the top of the masonry wall below. Snow and ice collects on the rowlock sills. When they melt, water can penetrate the sills and refreeze, resulting in deterioration. This scenario is a particular problem with the anchorage of these sills because they break apart.

When rowlock sills are used, they can be anchored using galvanized corrugated wall ties in the head joint between every fourth to sixth brick unit. When possible, I prefer that these anchors be attached to the backup wall on the vertical face, behind the sill.

It also is possible to extend flat strap anchors through the flashing. However, any penetrations through the flashing must be carefully sealed.

Click here to read full article from Masonry Construction

Related Articles
- Flashing in Siding Installations Potsdam NY
A constant problem that contractors see in siding installations is improper flashing or, even worse, no flashing at all. Relying on caulk alone to keep water from leaking into homes is not a good practice. Whether you're talking about wood, fiber-cement, or vinyl siding, three areas in particular can prove problematic.