Flashing Factors Fairport NY

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments in Fairport.

Local Companies

Professional Finishes
585-533-9140
28 academy dr.
rochester, NY
CO9 STEEL
585 301 7724
310 angelus dr
ROCHESTER, NY
Yurewich Victor
(845) 354-1362
75 Wilder Rd
Suffern, NY
25 Mason Inc
(718) 832-2388
121 25th St
Brooklyn, NY
A & J Masonry Construction Corp
(718) 845-4507
9408 Albert Rd
Jamaica, NY
DJM Equipment
585-223-4056
7216 Palmyra Road
Fairport, NY
LM Sanderson Construction Inc.
585 370 6076
891 Dewitt rd.
Webster, NY
Mastercraft Masonry I Inc
(718) 231-3077
271 E 233rd St
Bronx, NY
Zamboli Mason Inc
(631) 395-1900
581 Mastic Rd
Mastic, NY
Kelly Masonry Corp
(516) 739-8110
366 Sagamore Ave
Mineola, NY

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: October 1, 2005

Should flashing be used beneath rowlock brick window sills? If through-wall flashing is installed beneath these rowlocks, how are the sills anchored? If the anchors penetrate the flashing, does this lead to deterioration of the masonry below in freeze-thaw environments?

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments.

When they are used in freeze-thaw environments, however, the flashing beneath them is critical to prevent water from saturating the top of the masonry wall below. Snow and ice collects on the rowlock sills. When they melt, water can penetrate the sills and refreeze, resulting in deterioration. This scenario is a particular problem with the anchorage of these sills because they break apart.

When rowlock sills are used, they can be anchored using galvanized corrugated wall ties in the head joint between every fourth to sixth brick unit. When possible, I prefer that these anchors be attached to the backup wall on the vertical face, behind the sill.

It also is possible to extend flat strap anchors through the flashing. However, any penetrations through the flashing must be carefully sealed.

Click here to read full article from Masonry Construction