Flashing Factors East Meadow NY

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments in East Meadow.

Local Companies

Window Designs by Suzi
(914) 636-6859
23 Stephenson Blvd.
New Rochelle, NY
trinchese iron works and construction inc.
(718) 848-1954
3375 royal ave
oceanside, NY
DL Restoration & Builders Corp
718 275 3995
107-12 71st Road
Forest Hills, NY
Pro Qualtiy Home Improvements Inc.
631 393 6812
500 Bi-County Blvd.
Farmingdale, NY
Uvs Construction
(718) 554-0426
Beach 74Th St
Arverne, NY
x builders inc
347-952-1776
9031 171st st 2nd floor
jamaica, NY
slr general construction
1646 420 2006
173 morton blvd
plainview, NY
jose painting
347-694-9691
3758 101st
corona, NY
Citi Skyline contractors inc.
(917) 583-3312
68-01 Forest avenue
Ridgewood, NY
Gotham Builders
800-444-4923
203- 20 Rocky Hill Road
Bayside, NY
Data Provided by:
  

Provided By:

Source: MASONRY CONSTRUCTION MAGAZINE
Publication date: October 1, 2005

Should flashing be used beneath rowlock brick window sills? If through-wall flashing is installed beneath these rowlocks, how are the sills anchored? If the anchors penetrate the flashing, does this lead to deterioration of the masonry below in freeze-thaw environments?

Rowlock brick sills contain many joints and are particularly susceptible to water penetration. For this reason, I do not recommend their use in freeze-thaw environments.

When they are used in freeze-thaw environments, however, the flashing beneath them is critical to prevent water from saturating the top of the masonry wall below. Snow and ice collects on the rowlock sills. When they melt, water can penetrate the sills and refreeze, resulting in deterioration. This scenario is a particular problem with the anchorage of these sills because they break apart.

When rowlock sills are used, they can be anchored using galvanized corrugated wall ties in the head joint between every fourth to sixth brick unit. When possible, I prefer that these anchors be attached to the backup wall on the vertical face, behind the sill.

It also is possible to extend flat strap anchors through the flashing. However, any penetrations through the flashing must be carefully sealed.

Click here to read full article from Masonry Construction

Related Articles
- Flashing in Siding Installations East Meadow NY
A constant problem that contractors see in siding installations is improper flashing or, even worse, no flashing at all. Relying on caulk alone to keep water from leaking into homes is not a good practice. Whether you're talking about wood, fiber-cement, or vinyl siding, three areas in particular can prove problematic.
- Flashing and Sill Products East Meadow NY
- Home Exterior Products East Meadow NY
- Inner Corner at Base of Wall East Meadow NY
- High-Efficiency Products East Meadow NY
- Home Siding Tips East Meadow NY
- Green Products - Product Reviews East Meadow NY
- Flashing at Sills East Meadow NY
- Eco-Friendly Products East Meadow NY
Related Local Event
Long Island Building & Facility Maintenance Show
Dates: 5/5/09 - 5/8/20
Location: David S. Mack Sports & Exhibition Complex - Hofstra University
Hempstead, NY
View Details